Crouse-Hinds FlexStation™ EDSC2129 SA Factory Sealed Heavy Duty Through Feed Snap Switch Control Station With Switch, 120/277 VAC, 20 A, NEMA 3/7B/7C/7D/9E/9F/9G NEMA Rating
EDSC2129SA
MFG #: EDSC2129 SA
Requires Quote
Non-Stock Item
- Amperage Rating: 20 A
- Contact Mode: Maintained
- Country of Origin: MX
- Dimensions: 3-1/2 in W
- Finish: Natural
- Legend: ON/OFF
- Manufacturer Name: Eaton
- Material: Copper-Free Aluminum
- NEMA Rating: NEMA 3/7B/7C/7D/9E/9F/9G
- Number of Poles: 1
- Operator Type: Front
- Series: EDS
- Type: Factory Sealed Heavy Duty Through Feed
- Voltage Rating: 120/277 VAC
Crouse-Hinds series factory sealed enclosures are used to prevent arcing of enclosed device from causing ignition of a hazardous atmosphere external to the enclosure. Enclosures are used in conjunction with magnetic starters or contactors for remote control of motors.
- Item Features
- Application
- Standards
- Factory sealed enclosures are used to prevent arcing of enclosed device from causing ignition of a hazardous atmosphere external to the enclosure, in conjunction with magnetic starters or contactors for remote control of motors
- Reduce installation problems
- Eliminate external seals
- Lower installation costs
- Improve safety
- Are used with general purpose snap and pushbutton type switches
- Standard neoprene covers for front operated pushbuttons, prevents accumulation of dirt and entrance of water around operating shafts
- Mounting lugs and taper tapped hubs with integral bushing
- Large machine screws for fastening covers to bodies
- Lockout provisions on front operated pushbutton (marked "STOP" and "OFF") and all selector switch covers
- Lockout hole for padlock having 1/4 in hasp is provided when used with covers for front lever and side rocker type operation
- Close tolerances in machining of wide, mating flanges and journaled shafts and bearings for front button operation, produces flame tightness of enclosure joints
- On enclosure with front lever and side rocker type operating handles, threaded type shafts and bushings are used to ensure flame tightness
- Explosionproof, dust-ignitionproof, rain tight
- 3/4 in hub
Industrial Facilities and Factories, Facility, Power Distribution and Control Applications
CEC Certified|CSA C22.2 File No. 30|NEC Certified|UL File No. 1203