Square D™ TeSys™ GB2CB16 Circuit Breaker, 250/277 VAC/48 VDC, 10 A, 1 kA Interrupt, 1 Poles, Thermal/Magnetic Trip

GB2-CB16 MFG #: GB2CB16
Requires Quote
Square D™ TeSys™ Circuit Breaker, Series: GB2, 250/277 VAC/48 VDC, 10 A, 2 W Power, 50/60 Hz Frequency, 1 kA Interrupt, Thermal/Magnetic Trip, 138 A Trip, 1 Pole, Toggle Actuator, Cable Connection, IP20 Enclosure, Plate/Rail Mounting, -20 to 60 deg C, 74 mm H x 15 mm W x 67 mm D Dimensions
QTY
  • Category A conforming to IEC 60947-2, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 609
  • 50/60 Hz conforming to IEC 60947-2 network frequency
  • Icu = 50 kA at 230/240 VAC at 50/60 Hz, Icu = 1 kA at 48 VDC, Icu = 50 kA at 110 VAC 50/60 Hz, Icu =
  • 50 % at 110 VAC 50/60 Hz, 25 % at 230/240 VAC 50/60 Hz conforming to IEC 60947-2
  • By clips mounting mode
  • Horizontal/vertical mounting position
  • Toggle control type
  • 277 VAC 50/60 Hz conforming to CSA C22.2 No 14, 48 VDC, 250 VAC 50/60 Hz conforming to IEC 60947-2,
  • 4 kV conforming to IEC 60947-2 rated impulse withstand voltage
  • 2 W power dissipation per pole
  • 8000 cycles mechanical durability
  • 8000 cycles electrical durability
  • Connector 1 cable 0.75 to 6 sq-mm, 0.75 to 4 sq-mm, 0.75 to 4 sq-mm, 0.75 to 2.5 sq-mm - cable stiff
  • 1.2 N-m - on connector tightening torque
  • Shocks 22 Gn for 20 ms conforming to IEC 60068-2-27, vibrations 5 Gn, 5 to 110 Hz conforming to IEC
  • 2 9 mm pitches
  • TC protective treatment
  • IP20 conforming to IEC 60529 deg of protection
  • -40 to 80 deg C ambient air temperature for storage
  • 960 deg C conforming to IEC 60695-2-1 fire resistance
Category A conforming to IEC 60947-2, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 60947-5-1 utilization category
50/60 Hz conforming to IEC 60947-2 network frequency
Icu = 50 kA at 230/240 VAC at 50/60 Hz, Icu = 1 kA at 48 VDC, Icu = 50 kA at 110 VAC 50/60 Hz, Icu = 1.5 kA at 24 VDC conforming to IEC 60947-2
50 % at 110 VAC 50/60 Hz, 25 % at 230/240 VAC 50/60 Hz conforming to IEC 60947-2
By clips mounting mode
Horizontal/vertical mounting position
Toggle control type
277 VAC 50/60 Hz conforming to CSA C22.2 No 14, 48 VDC, 250 VAC 50/60 Hz conforming to IEC 60947-2, 277 VAC 50/60 Hz conforming to UL 1077 rated operational voltage
4 kV conforming to IEC 60947-2 rated impulse withstand voltage
2 W power dissipation per pole
8000 cycles mechanical durability
8000 cycles electrical durability
Connector 1 cable 0.75 to 6 sq-mm, 0.75 to 4 sq-mm, 0.75 to 4 sq-mm, 0.75 to 2.5 sq-mm - cable stiffness : solid - without cable end
1.2 N-m - on connector tightening torque
Shocks 22 Gn for 20 ms conforming to IEC 60068-2-27, vibrations 5 Gn, 5 to 110 Hz conforming to IEC 60068-2-6 mechanical robustness
2 9 mm pitches
TC protective treatment
IP20 conforming to IEC 60529 deg of protection
-40 to 80 deg C ambient air temperature for storage
960 deg C conforming to IEC 60695-2-1 fire resistance