- All connection kits used to terminate heating cables, including power connectors, splices, tees and
- In order to keep connections dry and corrosion resistant, connection kits shall be constructed of no
- The connection kit stand shall allow for up to 4 in of thermal insulation
- The connection kit shall use cold applied materials and shall not require the use of a heat gun, tor
- The connections are made with insulated crimp
- Black electrostatic-charge resistant glass-filled engineered polymer enclosure/stainless steel lid s
- 50 A maximum circuit breaker rating
- -40 deg F maximum installation temperature
- -75 to 132 deg F ambient
- 500 deg F maximum pipe temperature
- Type 4X/IP66/IP67 ingress protection
All connection kits used to terminate heating cables, including power connectors, splices, tees and connectors shall be approved for the respective area classification and approved as a system with the particular type of heating cable in use
In order to keep connections dry and corrosion resistant, connection kits shall be constructed of nonmetallic, electrostatic, charge-resistant, glass-filled, engineered polymer enclosure rated NEMA 4X
The connection kit stand shall allow for up to 4 in of thermal insulation
The connection kit shall use cold applied materials and shall not require the use of a heat gun, torch or hot work permit for installation
The connections are made with insulated crimp
Black electrostatic-charge resistant glass-filled engineered polymer enclosure/stainless steel lid screws/silicone rubber lid gasket
50 A maximum circuit breaker rating
-40 deg F maximum installation temperature
-75 to 132 deg F ambient
500 deg F maximum pipe temperature
Type 4X/IP66/IP67 ingress protection