Raychem® E-100-A High Profile End Seal Kit, For Use With BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTVCT and VPL-CT Industrial Parallel Heating Cable

E-100-A MFG #: E-100-A
Requires Quote
Raychem® End Seal Kit, High Profile, For Use With: BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTVCT and VPL-CT Industrial Parallel Heating Cable, 7 in H
QTY
  • All connection kits used to terminate heating cables, including power connectors, splices, tees and
  • In order to keep connections dry and corrosion-resistant, connection kits shall be constructed of no
  • The connection kit stand shall allow for up to 4 in of thermal insulation
  • The connection kit shall use cold applied materials and shall not require the use of a heat gun, tor
  • The connection kit shall be rated to a minimum installation temperature of -40 deg F, minimum usage
  • Terminals shall be spring clamp wire connection type to provide reliable connection, maintenance fre
  • -75 to 132 deg F ambient temperature
  • 480 VAC maximum operating voltage
  • 2 in OD insulation
  • High performance glass filled engineered polymer
All connection kits used to terminate heating cables, including power connectors, splices, tees and connectors shall be approved for the respective area classification and approved as a system with the particular type of heating cable in use
In order to keep connections dry and corrosion-resistant, connection kits shall be constructed of nonmetallic, electrostatic, charge-resistant, glass filled, engineered polymer enclosure rated type 4X(IP66)
The connection kit stand shall allow for up to 4 in of thermal insulation
The connection kit shall use cold applied materials and shall not require the use of a heat gun, torch or hot work permit for installation
The connection kit shall be rated to a minimum installation temperature of -40 deg F, minimum usage temperature of -60 deg F and maximum pipe temperature of 500 deg F
Terminals shall be spring clamp wire connection type to provide reliable connection, maintenance free operation and ease of reentry
-75 to 132 deg F ambient temperature
480 VAC maximum operating voltage
2 in OD insulation
High performance glass filled engineered polymer