Crouse-Hinds Chico® A CHICO A05 Sealing Compound, 115 cu-in Pail, Light Gray
CHICO A05
MFG #: CHICO A05
Requires Quote
Non-Stock Item
- Color: Light Gray
- Composition: Cement, Alumina, Chemicals, Bassanite, Haturite
- Container Size Range: 115 cu-in
- Container Type: Pail
- Country of Origin: US
- Curing Time: 8/72 hr
- Drying Time: 60 to 70 min
- Flammability Rating: Non-Flammable
- Form: Powder
- Manufacturer Name: Eaton
- Specific Gravity: 3
- Temperature Rating: -40 to 165 deg F
Crouse-Hinds series Chico® sealing compounds and fiber are used to form a seal around each electrical conductor and between them and inside of the sealing fitting to restrict the passage of gases, vapors or flames through the sealing fitting. Chico® A sealing compound is a water soluble powder that can be easily mixed and poured. The dense compound expands slightly when hardening and bonds to inner walls of sealing fittings. Chico® A-P Intrapak is packaged in a two compartment plastic pouch with precise amount of water for mixing. No measuring is required, speeding up the installation process. Chico® X fiber forms a dam between the integral bushing of the sealing fitting and the end of the conduit and around the electrical conductors entering the hub. It is a mineral wool that packs easily, forming around each conductor. Chico® A, Chico® A-P and Chico® X are approved for use in Class I, Division 1, Groups A, B, C, D and Class II, Division 1, Groups E, F, G hazardous areas.
- Standards
- Application
- Item Features
Class I, Division 1, Groups A/B/C/D
Industrial Facilities andFactories Applications
- A water soluble powder that can be easily mixed and poured
- The compound, unusually dense, expands slightly when hardening and bonds to inner walls of sealing fitting
- Compound hardens in 60 to 70 min
- Chico® A ambient temperature range (after curing) is -40 to 165 deg F
- Chico® A cure time is 8 hr for Class I, groups C and D application and 72 hr for Class I, groups A and B application
- Forms a seal around each electrical conductor and between them and inside of the sealing fitting to restrict the passage of gases, vapors or flames th